“Full/Empty” Calibration

Perform calibration in the fuel, in which the fuel level sensor Omnicomm LLS will operate.

  1. Fill the measuring container with fuel
  2. Immerse the Omnicomm LLS sensor in the fuel to the full length of the measuring piece
  3. Wait for green indicator “Level Stabilized” to appear.
    In the “Settings” tab, “Full/Empty Calibration” section, press “Full” button, then the value corresponding to the full tank will be set
  4. Take the Omnicomm LLS sensor out of the container and allow the fuel to flow down the measuring piece for 1 minute. In the “Full/Empty Calibration” section, press “Empty” button, then the value corresponding to the empty tank will be set
  5. Press the “Record to Device” button